Mounting an SRX4600 Firewall on Four Posts of a Rack or Cabinet
Before mounting the firewall on four posts of a rack:
Verify that the site meets the requirements described in Site Preparation Checklist for the SRX4600 Firewall.
Place the rack in its permanent location, allowing adequate clearance for airflow and maintenance, and secure it to the building structure.
Read General Safety Guidelines and Warnings, with particular attention to Chassis and Component Lifting Guidelines.
Ensure that you have the following parts and tools available:
Phillips (+) screwdriver, number 2
Six Phillips 4-40 flat-head mounting screws (provided with the four-post rack-mount kit)
Eight Phillips 4x6-mm flat-head mounting screws (provided with the four-post rack-mount kit)
One pair each of flush or 2-in.-recess front-mounting brackets
One pair of side mounting rails
One pair of rear mounting blades
Screws to secure the chassis and the rear mounting blades to the rack (not provided)
You can mount an SRX4600 Firewall on four posts of a 19-in. rack or cabinet by using the four-post rack-mount kit. The remainder of this topic uses rack to mean rack or cabinet.
Space the front and rear rack rails between 23.5 in (59.7 cm) to 30.25 in (76.8 cm) front-to-back.
One person must be available to lift the firewall while another secures it to the rack.
If you are mounting multiple units on a rack, mount the heaviest unit at the bottom of the rack and mount the other units from the bottom of the rack to the top in decreasing order of the weight of the units.
To mount the firewall on four posts of a rack: