Installing the MX2010 Mounting Hardware for a Four-Post Rack or Cabinet
Installing Cage Nuts, If Needed
Insert cage nuts, if needed, into the holes listed in Table 1 and Table 2. The hole distances are relative to the standard U division on the rack that is aligned with the bottom of the mounting shelf.
To install cage nuts in a four-post rack:
- On the rear side of both rack rails, insert cage nuts in the holes specified for the four-post mounting shelf. Install the cage nuts in the front of the front rail (see Table 1).
- On the front side of both rack rails, insert cage nuts in the holes specified for mounting the chassis. Install the cage nuts in the front of the front rail (see Table 1).
Hole |
Distance Above U Division |
|
---|---|---|
6 |
3.25 in. (8.3 cm) |
1.86 U |
5 |
2.63 in. (6.7 cm) |
1.5 U |
4 |
2.00 in. (5.1 cm) |
1.14 U |
3 |
1.50 in. (3.8 cm) |
0.86 U |
2 |
0.88 in. (2.2 cm) |
0.50 U |
1 |
0.25 in. (0.6 cm) |
0.14 U |
Hole |
Distance Above U Division |
|
---|---|---|
110 |
63.88 in. (162.2 cm) |
36.50 U |
101 |
58.63 in. (148.9 cm) |
33.50 U |
92 |
53.38 in. (135.6 cm) |
30.50 U |
83 |
48.13 in. (122.2 cm) |
27.50 U |
74 |
42.88 in. (108.9 cm) |
24.50 U |
65 |
37.63 in. (95.6 cm) |
21.50 U |
56 |
32.38 in. (82.2 cm) |
18.50 U |
47 |
27.13 in. (68.9 cm) |
15.50 U |
38 |
21.88 in. (55.6 cm) |
12.50 U |
29 |
16.63 in. (42.2 cm) |
9.50 U |
20 |
11.38 in. (28.9 cm) |
6.50 U |
11 |
6.13 in. (15.6 cm) |
3.50 U |
The holes in the front-mounting flanges are spaced at 3 U (5.25 in. (13.3 cm).
See Also
Installing the Four-Post Mounting Shelf
A mounting shelf is required for installing the router in a four-post rack or cabinet. The shelf is not required for installing the router in an open-frame rack.
To install the four-post mounting shelf (see Figure 1):
See Also
Removing the Center-Mounting Brackets
The center-mounting brackets are not used for a four-post rack, and must be removed from the chassis.
To remove the center-mounting brackets from the chassis: